Product Details
IG 541 is used to extinguish fires in sensitive areas, such as: call centers, computers, vulnerable devices, machines, etc.
IG 541 is a mixture of Nitrogen (52%), Crude (40%) and Carbon Dioxide (8%), is odorless, colorless, non-corrosive and because it is a gas that is free in the atmosphere, does not affect ozone and has zero effect on increasing atmospheric heat.
IG 541 extinguishes the fire by reducing the oxygen level in the space below 13% (point where most materials stop burning).
At the same time the percentage of Carbon Dioxide contained in the mixture, protects anyone trapped in the fire area from low oxygen levels. This is because when the Carbon Dioxide contained in the blood and which controls human respiration increases, then the transport of oxygen to the brain increases accordingly. Thus, if a person is exposed to an environment with an oxygen content of less than 21%, which is normal, then he develops hypoxia, which is a dangerous condition. The presence of Carbon Dioxide in IG 541 dilates the arteries that supply blood to the brain, resulting in an increase of about 15% in the oxygen transported to it compared to the normal atmosphere. IG 541 is stored in bottles with a capacity of 16, 40, 60, 67.5 and 80 liters.
SYSTEM DESCRIPTION
Single or Multiple Cylinder systems are applied depending on the volume of the protected areas.
In a Multi-Cylinder System, the “Pilot” Cylinder is used to activate the system’s cylinders.
The “Pilot” Cylinder is activated automatically using the detonator which is fired from the Fire Detection-Extinguishing Panel of the System. The Panel is commanded by a Detection System consisting of pairs of Heat Detectors and Smoke Detectors. It is activated manually either by pushing the Shutter Piston or by Remote Manual Activation Button.
The “Pilot” Cylinder Shutter is connected via the EPDM High Pressure Hose to the Shutter of the 1st cylinder of the system. In essence, when the “Pilot” Cylinder is activated, the propellant Gas pneumatically activates the Shutters of the main Dioxide Bottles of the System (the Shutters of the main Bottles of the System are connected with EPDM High Pressure Hoses). Once the main Cylinders of the System are activated, the Extinguishing Material is forwarded through Flexible EPDM High Pressure Pipes to the Collector of the System from where it is led to Nozzles.
THE SYSTEM INCLUDES
Cylinders
Certified Cylinders IG541 16Lt, 40Lt, 50Lt, 67.5Lt and 80Lt with Automatic, Manual or Pneumatic Activation Shutter (with or without Manometer), Protection Disc and Heavy Duty Stands.
• Certified “Pilot” Cylinder 3lt (2Kg) with Automatic, Manual or Pneumatic Activation Shutter and Heavy Press Base.
Collector accessories
– Cross section collector pipe from 1¼ ”to 3”
– Tuff Collector Cross section from 1¼ ”to 3”
– Collector plug size from 1¼ ”to 3”
– Section Collector Shrinkage ¼ ”=> ¾”, 2 ”=> 1”, 2½ ”=> 1½”, 3 ”=> 2”.
– Non-return Valve ¾ ”.
EPDM Hoses
• EPDM High Pressure Hose “Pilot” Cylinder connection with the Shutter of the first Cylinder of Multi-Cylinder System
• Multi-Cylinder System High Pressure Hose EPDM Hose
• EPDM High Pressure Hose Connecting System Cylinders with Non-return Manifold Valve
• EPDM High Pressure Hose for Connecting a Cylinder System to a Nozzle Network
Other Components
– Breast (3/8 ”- 3/8”) – for the connection of Flexible EPDM Pipes to the Cylinder Shutters of the System
– 3/8 ”Cap for Sealing the Outlet of the Pilot Cylinder Shutter and the last Cylinder of the System
– Nozzles from ½ ”to 1 ½”
– Output Pressure Regulator IG-541 (from 200bar to 60bar)
Fire detection
• Certified Table of four zones
• Audiovisual Siren
• Manual System Activation Button
• Extinguish Cancel Button
• Heat Detectors (Thermal Limit or Thermo-Differential)
• Smoke Detectors
• STOP GAS plate
TECHNICAL SPECIFICATIONS
The Recommendation of IG 541 is:
NITROGEN 52% ± 4%, SLOW 40% ± 4%,
CARBON DIOXIDE 8% ± 4%
CERTIFICATES
ISO 9809 – 1 EN 1964 – 1 π 99/36 / EC
CE BOTTLE OF PILOT 97/23 / EC (TUV) – CE CLOSER (BAM)
CE 0589